Figure 39: GOOSE data attributes imported
4.6.4.5

GOOSE input mapping

This section describes the configuration process of GOOSE input mapping in HMI500 menu
Configuration/Binary Module/Inputs/Details.
IEC18000562 V1 EN-US
Figure 40: Configuration/ Binary module/ Inputs/ Details/ Contact mode – GOOSE Input
Table 11:
Menu Items
Assigned GOOSE data
Attribute
Selection – Unassigned
GOOSE data Attributes
Selection – Assign
Selection – Deassign
Selection – GOOSE data
attribute filter
Distributed busbar protection REB500
Operation manual
To simplify GOOSE engineering in REB500, the import of GOOSE signals is
limited to specific logical nodes (for example, PTRC).
GOOSE Input menu items
Description
If a REB500 Signal has assigned to a GOOSE data attribute then the
name of the attribute is listed in this field
List of GOOSE data attributes which can be assigned to the
selected Input signal. See
Confirms the mapping of the selected attribute to the REB500
Signal. The Assign button is enabled after the Station
configuration file (SCD) has been imported.
Breaks the connection between the GOOSE data attribute and the
REB500 input signal. The GOOSE data attribute can be assigned to
another REB500 Signal.
See
Table 12
© Copyright 2019 ABB. All rights reserved
15000037-IEC18000557-1-en.vsdx
15000042-IEC18000562-1-en.vsdx
Figure
41.
Section 4
HMI500
GUID-412DEE24-DC4A-4536-9699-43BC440EBEC2 v1
47