Testing Menu; Test Mode - ABB RELION REB500 Operation Manual

Distributed busbar protection, version 8.3 iec
Hide thumbs Also See for RELION REB500:
Table of Contents

Advertisement

Section 4
HMI500
Setting menu item
Release logic/matrix
System response
Activate/deactivate
device
CB inspection
Event memory
Time
4.8

Testing menu

4.8.1

Test mode

The test generator is activated by opening the Testing menu, selecting Test mode. A tick
appears next to the menu item, Test mode is added to the status line at the bottom of the
screen and the Test mode dialog box opens.
The test generator is used in conjunction with the Status of binary inputs/outputs dialog box
(has to be opened by the operator), (see
When the test generator is active, the statuses of the tripping commands cannot change.
IEC18000502 V1 EN-US
Figure 56: Test mode
62
Av
Technical Manual section
Release logic/matrix
System response
see
Commissioning Manual
see
Commissioning Manual
Event memory
Time synchronization
Switching to the test mode while the protection is in operation should only be
undertaken by especially trained personnel. Incorrect manipulations can cause
false tripping, for example, by inadvertently operating a tripping relay,
simulating an incorrect isolator or circuit-breaker status or activating a
tripping input (for example, External TRIP).
© Copyright 2019 ABB. All rights reserved
Application Manual
section
Section
4.5.4).
Distributed busbar protection REB500
1MRK 500 132-UEN B
-
-
-
-
-
-
GUID-473177D3-8944-4424-A7C2-B73F6E5F326E v1
GUID-905FC498-982F-4D9B-869D-81E785382C41 v2
12000095-IEC18000502-1-en.vsdx
Operation manual

Advertisement

Table of Contents
loading

Table of Contents