Section 4
HMI500
Table 14:
Menu items
GCB Name
Caption
App ID
MAC Address
VLAN ID
VLAN Priority
Min Time
Max Time
Add GCB
Delete GCB
4.6.5.2

Defining signals for GOOSE send

This section describes the configuration of the "GOOSE output" mapping which is done in
HMI500 menu in Configuration/Binary Module/Outputs/Details.
Only specific Signals can be assigned to GOOSE. In the Details Tab of the Binary Module/
Outputs the menu item GOOSE control block assignment is only shown for these specific
signals.
52
GCB configuration Menu Items
Description
Unambiguously identification of the GCB
within the scope of the LLN0. Defined by the
System.
Attribute that allows a user to assign an
identification for the GOOSE message.
Unique Identifier of GOOSE messages
according to IEC 61850-8-1 Appendix C.
MAC address to which the GOOSE message is
to be sent. The address shall be an Ethernet
address that has the multicast bit set TRUE.
Range of values from 0 to 4095 according to
IEEE 802.1Q.
Range of values 0 to 7 according to IEEE
802.1Q.
As defined in IEC 61850-6 the sending delay
on a data change between the first
immediate sending of the change and the
first repetition in ms.
As defined in IEC 61850-6 the source
supervision time in ms (supervision heartbeat
cycle time).
Insert a new item at the end of the list.
Deletes the selected item
Only signals which are mapped to a GOOSE control block are sent in GOOSE
messages.
For all mapped signals the name of the GCB Name is listed in the GOOSE
column in the Overview tab of the Binary module/ Outputs dialog box.
The combined tripping signals are less flexible than the tripping
logic of the Trip relays output assignment in the Details Tab of
Configuration /Binary Module — Outputs.
If a phase selective function trips that is 23315_BFP TRIP L1
(PTRC.phsA on GOOSE) then also system internally the 23315_BFP
TRIP L1 is set. As a consequence for GOOSE the PTRC. general is
always TRUE on a trip. This in parallel with the phase specific
PTRC.phsx (x = A,B,C,neut) on GOOSE.
© Copyright 2019 ABB. All rights reserved
1MRK 500 132-UEN B
IEC 61850 identification
GoCBName
GoID (Ed 2)
appID (Ed1)
APPID
DstAddress.Addr
DstAddress.VID
DstAddress.PRIORITY
MinTime
MaxTime
GUID-E887B7F0-A4A2-4864-A005-90A47D83DC53 v1
Distributed busbar protection REB500
Operation manual
Default
0
0
4
4
10000