Test Trip - ABB RELION REB500 Operation Manual

Distributed busbar protection, version 8.3 iec
Hide thumbs Also See for RELION REB500:
Table of Contents

Advertisement

1MRK 500 132-UEN B
Table 23:
Trip
BFP TRIP T1
OCDT TRIP
OCDT TRIP
TRIP
1) Second OCDT TRIP is caused by the Bay Protection function (no value entry available for this type of
functions)
Table 24: Example for a trip list viewed on Central Unit
Trip
BBP TRIP L1
BFP TRIP T1
OCDT TRIP
1) If all feeders in a protection zone are excluded from phase comparison then the value
phase differences (see section
2) If only one feeders in a protection zone is included for phase comparison then the value
phase differences (see section
3) The measuring range of the phase difference is 0..3142 mrad (0° .. 180°)
The red Protection indicator LED signals the trip state:
Off: No pending trip in list
On: Pending or latched trips in list
The protection system and all signals can be reset by choosing Clear/Reset all latched LEDs
and Lists on the LHMI, or equivalently by setting the signal 31810_External reset, for example,
generated by pressing the RESET button.
5.6

Test Trip

The REB500 system provides a test facility to activate and deactivate a test trip per bay. For
this purpose the signal 21120_EXT_TEST_TRIPcan be set and reset via bay. For this purpose
the signal 21120_EXT_TEST_TRIP can be set and reset via the LHMI Test Trip menu.
The LHMI Test Trip can be combined with a current criteria, so that the test trip is only issued
if the current of one phase does not exceed a certain factor of the rated current.
Distributed busbar protection REB500
Operation manual
Example for a trip list viewed on Bay Unit
Date
2015-11-23 09:05:46
2015-11-23 09:05:46
2015-11-23 09:05:46
1)
2015-11-23 09:05:46
Date
2015-11-23 09:05:46
2015-11-23 09:05:46
2015-11-23 09:05:46
Phase comparison ) in the REB500 Application manual
Phase comparison in the REB500 Application manual
If the signal 11115_Ext_Test_TRIP and LHMI Test Trip function are configured
and used simultaneously, the signal 21120_EXT_TEST_TRIP results from an OR
function of both possible inputs.
To enter LHMI Test Trip menu a user authentication is mandatory in case that
user account management is enabled. For details about the user account
Cyber security guideline .
management see
© Copyright 2019 ABB. All rights reserved
Source
Value
Bayname 1
L1 3604A
Bayname 1
3604A
Bayname 1
-
Bayname 1
-
Source
1)2)3)
Value
Zone BB01
Id =
3604A
Bayname 1
3604A
Bayname 1
L2 0A
L3 0A
L0 3604A
-
-
-
-
-
-
-
-
-
Ih =
Ph-Diff =
4240A
175mrad
-
-
-1 is shown for the
0 is shown for the
GUID-CC447285-5510-4C69-AF36-45707400DE1F v1
Section 5
Local HMI
79