Protection Zone Measurements; Overview - ABB RELION REB500 Operation Manual

Distributed busbar protection, version 8.3 iec
Hide thumbs Also See for RELION REB500:
Table of Contents

Advertisement

Section 4
HMI500
IEC18000490 V1 EN-US
Figure 9:
4.5.2

Protection zone measurements

This dialog displays the actual values of measured variables for each protection zone
(restrained differential current of the bus bar protection function). The protection zones are
determined by the positions of the isolators and the bus-tie breakers (bus bar image).
4.5.2.1

Overview

The currently active protection zones are listed in order showing the associated sections of
busbar and the differential current per phase or in the neutral. The overview is not updated
automatically. Click Refresh to update the list.
A protection zone to which no measurement has been assigned, that is no bay unit current is
processed by the busbar protection algorithm, is shown as invalid.
Protection zones that have been connected, for example, via a pair of feeder isolators or a
longitudinal isolator, are also presented.
20
Updated single-line diagram
© Copyright 2019 ABB. All rights reserved
1MRK 500 132-UEN B
12000081-IEC18000490-1-en.vsdx
GUID-514CE160-B685-4E58-86EB-DEBAEB29FAB3 v1
GUID-DD79AA17-F3A5-493E-B63A-4BB785588BED v2
Distributed busbar protection REB500
Operation manual