ABB RELION REB500 Operation Manual page 49

Distributed busbar protection, version 8.3 iec
Hide thumbs Also See for RELION REB500:
Table of Contents

Advertisement

1MRK 500 132-UEN B
Table 10:
Step REB500
configuration tool
HMI500
1
Pre-configuration:
2
The REB500 IEC
61850-8-1 model is
exported in an ICD
file.
3
The REB500 ICD
file is transferred
to the system
engineering tool
4
-
5
-
6
-
7
The available
GOOSE data
attributes are
imported (from
SCD file)
Table continues on next page
Distributed busbar protection REB500
Operation manual
GOOSE engineering process
System
engineering tool
-
REB500
System must
be
configured
System name
must be
defined
GOOSE client
must be
enabled
-
-
The REB500 ICD
file is imported
The data flow
engineering is
made in the
System
engineering tool
Export of the
Station
configuration
description
(SCD file) and
transfer to the
HMI500
-
© Copyright 2019 ABB. All rights reserved
Remark
Enabling GOOSE Client (see
See
Figure 36
and
Figure 37
In addition to the ICD file that describes the IED functions, the
project-specific configuration file is also exported:
Edition 1: CID file (.cid)
Edition 2: IID file (.iid)
Selection of the Edition
Configuration/Communication/SCS Configuration/IEC
61850-8-1 options/Edition x (see
This Export SCS data process is used initially and after a
configuration change.
Each time the export is started, the original
values of REB500 setting parameters are
implemented.
The IED name of the REB500 in the System engineering tool
must match the System name in the REB500 configuration
tool.
Setting instruction: For correct operation the GOOSE max
repetition time should be set to 1 second.
Containing GOOSE data set, report control block, source IED
and destination IED
Configuration/Communication/SCS Configuration/IEC
61850-8-1 options/Import GOOSE data attributes button
(see
Figure
38).
Section 4
Figure
35)
Figure
38)
HMI500
43