Installing A Repo Switch - Eaton Power Xpert 9395 Series Installation And Operation Manual

Hide thumbs Also See for Power Xpert 9395 Series:
Table of Contents

Advertisement

UPS System Installation
4.8

Installing a REPO Switch

A latching-type Remote Emergency Power-off (REPO) switch can be used in an emergency to shut down the
UPS and remove power to the critical load from a location away from where the UPS is installed. Figure 4-19
shows a REPO switch.
NOTE
NOTE
NOTE
NOTE
NOTE
NOTE
To Install a REPO switch:
1.
Verify the UPS system is turned off and all power sources are removed. See Chapter 7, "UPS Operating
Instructions"" for shutdown instructions.
2.
Securely mount the REPO switch. Recommended locations include operator's consoles or near exit
doors. See Figure 3-7 for enclosure dimensions and wiring knockouts.
3.
Unfasten the front door latch and swing the door open (see Figure 4-1).
Figure 4-19. REPO Switch
4.
Remove the door. Remove the retaining screw located inside the door at the bottom hinge pivot point,
then lift the door off. Retain the hardware for later use.
5.
Remove one top screw and two bottom screws securing the UPS center front panel (see Figure 4-2). Lift
the panel straight up to remove it from the panel hanger bracket at the top of the cabinet.
TM
4-24
Power Xpert
Before installing a REPO switch, verify that the UPS was installed according to the
instructions in paragraphs 4.2 through 4.7.
When installing the REPO switch, you must install conduit between the device and
the UPS cabinet for wiring the switch.
Remove the UPS cabinet interface entry conduit landing plates to drill or punch
holes (see Figure 4-4).
The REPO switch must be a normally-open or normally-closed latching–type switch
not tied into any other circuits.
This procedure is intended to be used for the installation of the Eaton-supplied
REPO switch. If installing another manufacturer's switch, use this procedure only as
a guide.
The REPO switch wiring must be in accordance with NEC Article 725 Class 2
requirements.
REPO Switch (Front View)
9395 UPS (300 kVA) Installation and Operation Manual 164201728—Rev 10
Contact Block (Back View, Faceplate Removed)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Power xpert 9395-300

Table of Contents