Installing An Optional Remote Monitor Panel - Eaton Power Xpert 9395 Series Installation And Operation Manual

Hide thumbs Also See for Power Xpert 9395 Series:
Table of Contents

Advertisement

Installing Options and Accessories
Table 5-4. Pull-Chain Wiring Terminations with MOBs
From
UPS 1 CAN Bridge Card J3–1 (Alarm)
UPS 1 CAN Bridge Card J3–2 (Alarm Return)
UPS 1 TB2–1 (Pull Chain)
UPS 1 TB2–2 (Pull Chain Common)
UPS 2 CAN Bridge Card J3–1 (Alarm)
UPS 2 CAN Bridge Card J3–2 (Alarm Return)
UPS 2 TB2–1 (Pull Chain)
UPS 2 TB2–2 (Pull Chain Common)
UPS 3 CAN Bridge Card J3–1 (Alarm)
UPS 3 CAN Bridge Card J3–2 (Alarm Return)
UPS 3 TB2–1 (Pull Chain)
UPS 3 TB2–2 (Pull Chain Common)
UPS 4 CAN Bridge Card J3–1 (Alarm)
UPS 4 CAN Bridge Card J3–2 (Alarm Return)
UPS 4 TB2–1 (Pull Chain)
MOB 1 Aux 2 Com
MOB 2 Aux 2 Com
MOB 3 Aux 2 Com
5.4
Installing an Optional Remote Monitor Panel II
To install RMP II wiring:
1.
Verify the UPS system is turned off and all power sources are removed. See Chapter 7, "UPS Operating
Instructions" for shutdown instructions.
2.
Perform the procedure listed in paragraph 5.2.
NOTE
3.
Securely mount the RMP II at the desired location. See Figure 5-12 for mounting hole locations.
NOTE
4.
Remove the UPS cabinet top interface conduit landing plates to drill or punch conduit holes (see
Figure 4-4).
5.
Reinstall the conduit landing plate.
6.
Install conduit between the UPS and RMP II. See Figure 5-12 for RMP II knockout hole location.
TM
5-8
Power Xpert
MOB 1 Aux 1 NC
MOB 1 Aux 1 Com
MOB 1 Aux 2 NO
UPS 2 TB2–2 (Pull Chain Common)
MOB 2 Aux 1 NC
MOB 2 Aux 1 Com
MOB 2 Aux 2 NO
UPS 3 TB2–2 (Pull Chain Common)
MOB 3 Aux 1 NC
MOB 3 Aux 1 Com
MOB 3 Aux 2 NO
UPS 4 TB2–2 (Pull Chain Common)
MOB 4 Aux 1 NC
MOB 4 Aux 1 Com
MOB 4 Aux 2 NO
MOB 2 Aux 2 Com
MOB 3 Aux 2 Com
MOB 4 Aux 2 Com
If mounting to a hollow wall, secure the enclosure to a wood or metal stud within
the wall. Do not use hollow wall anchors.
When installing signal wiring for CAN card J3 terminals, conduit must be installed
between the device and the UPS cabinet.
9395 UPS (300 kVA) Installation and Operation Manual 164201728—Rev 10
To
Function
MOB Open Alarm
Pull Chain
Pull Chain Common
MOB Open Alarm
Pull Chain
Pull Chain Common
MOB Open Alarm
Pull Chain
Pull Chain Common
MOB Open Alarm
Pull Chain
Pull Chain MOB Common