Chapter 6

Understanding UPS Operation

6.1

UPS System Overview

The Power Xpert 9395 UPS is a continuous-duty, solid-state, transformerless (at 480 Vac), three-phase, true
online system that provides conditioned and uninterruptible AC power to the UPS system's output and critical
load.
The basic system consists of a rectifier, battery converter, inverter, monitoring/operation control panel,
integrated communication server, and digital signal processor (DSP) logic. Figure 6-1 shows the main elements
of the UPS system.
AC Input to
Rectifier/
Charger
AC Input to
Bypass
Figure 6-1. Main Elements of the UPS System
If utility power is interrupted or falls outside the parameters specified in Chapter 10, "Product Specifications"
the UPS uses a backup battery supply to maintain power to the critical load for a specified period of time or
until the utility power returns. For extended power outages, the UPS allows you to either transfer to an
alternative power system (such as a generator) or shut down your critical load in an orderly manner.
The emergency bypass consists of a continuous-duty static switch and backfeed protection contactor K5. The
backfeed protection contactor is located in series with the static switch. For manual transfers to bypass, the
static switch is also used. The static switch is armed and ready during both types of transfers.
Battery Cabinet or
Battery String
Input
Breaker
Input
CB1
Contactor
(optional)
K1
Rectifier
TM
Power Xpert
9395 UPS (300 kVA) Installation and Operation Manual 164201728—Rev 10
Battery
Battery
Breaker
Battery
Contactor
K2
Battery
Converter
Inverter
Power Module
Digital
Metering
Static
Switch
Backfeed
Protection
Contactor
K5
UPS Cabinet
Output
Contactor
K3
AC Output
to Critical
Load
6-1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Power xpert 9395-300

Table of Contents