Figure 40. Eaton 93Pm-L 200 Ups System Oneline; Understanding Ups Operation - Eaton 93PM-L Installation And Operation Manual

20 – 200 kw 208v ups
Hide thumbs Also See for 93PM-L:
Table of Contents

Advertisement

Understanding UPS Operation

Figure 40. Eaton 93PM-L 200 UPS System Oneline

UPS CABINET
UPMs 2-10
FUSE
RECTIFIER
SWITCHGEAR
RECTIFIER
INVERTER
INVERTER
SWITCHGEAR
FUSE
BATTERY
CONVERTER
BATTERY
SWITCHGEAR
FUSE
NOTES:
1. AC INPUT TO RECTIFIER IS NOT USED IN SINGLE FEED CONFIGURATION.
2. DASHED LINES INDICATE OPTIONAL UPM'S. CONFIGURABLE FROM 1-10 UPMS.
3. BACKFEED PROTECTION IS NOT PROVIDED AS A PART OF UPS. CUSTOMER
SUPPLIED BYPASS INPUT BREAKER WITH 48-60VDC SHUNT TRIP IS REQUIRED.
110
Eaton 93PM-L 20–200kW (208V) UPS Installation and Operation Manual 164000724—Rev 01
AC INPUT TO
RECTIFIER
A
E1,E2,E3
UPM 1
FUSE
RECTIFIER
SWITCHGEAR
RECTIFIER
INVERTER
INVERTER
SWITCHGEAR
FUSE
BATTERY
CONVERTER
BATTERY
SWITCHGEAR
FUSE
E4,E5
C
AC INPUT TO
BYPASS
(SEE NOTE 3)
B
E6,E7,
E8,E12
OPTIONAL
SINGLE-FEED
JUMPER
FUSE
STATIC
SWITCH
AC OUTPUT
LOAD
E9,E10,
D
E11,E12
BATTERY
BREAKER
EXTERNAL
BATTERY
CABINET
TO

Advertisement

Table of Contents
loading