Warning Label - Daikin Altherma 3 R F Installer's Reference Manual

Hide thumbs Also See for Altherma 3 R F:
Table of Contents

Advertisement

16
|
Technical data

16.9.2 Warning label

Installer reference guide
264
WARNING TO USER
■ Do not remove or adjust any component part of this installation.
Contact the installer.
■ Should the system develop a fault, switch the system off and
contact the installer.
WARNING TO INSTALLER
■ This installation is subject to building regulation approval,
notify Local Authority of intention to install.
■ Use only manufacturer's recommended spare parts.
Contact your local Daikin dealer.
■ Installed by
name
address
tel. No.
completion date
TECHNICAL SPECIFICATIONS
■ Maximum water supply pressure to pressure reducing valve: 16 bar
■ Operating pressure/set pressure of pressure reducing valve: 3.5 bar
■ Maximum primary working pressure (heating):
■ Maximum flow temperature:
■ Expansion vessel pre-charge pressure:
■ Expansion valve setting:
■ Temperature and pressure relief valve
replacement part No.:
■ Operating pressure of temperature and pressure
relief valve:
■ Operating temperature of temperature and pressure
relief valve:
■ Operating temperature of thermal cut-out (2 pieces):
■ Primary heating power input:
EHVH04SU18EA6V
EHVH04SU23EA6V
EHVH08SU18EA6V
EHVH08SU23EA6V
■ Primary flow rate to reach primary heating power input:
■ Standing heat loss:
EHVH04SU18EA6V
EHVH04SU23EA6V
EHVH08SU18EA6V
EHVH08SU23EA6V
■ Model
storage capacity
180 l
EHVH04SU18EA6V
EHVH04SU23EA6V
220 l
EHVH08SU18EA6V
180 l
220 l
EHVH08SU23EA6V
■ Maximum design pressure:
■ Rated volume heat exchanger:
EN12897: 2016
2.5 bar
o
65
C
3.5 bar
8 bar
302810P
10 bar
o
95
C
o
89
C
3.7 kW
4.2 kW
3.7 kW
4.2 kW
15 l/min
1.35 kWh/
24h
1.76 kWh/
24h
1.35 kWh/
24h
1.76 kWh/
24h
mass of unit when full
299 kg
348 kg
299 kg
348 kg
10 bar
9.1 l
4P631624-1
ERGA04~08EAV3(A) + EHVH04+08SU18+23EA6V
Daikin Altherma 3 R F
4P629090-1 – 2020.08