9.3.7 To connect the space cooling/heating ON/OFF output

ERGA04~08EAV3(A) + EHVH04+08SU18+23EA6V
Daikin Altherma 3 R F
4P629090-1 – 2020.08
2
1
X2M
7
9
A4P
Y1
YC
A
B
A
B
a Installation of EKRP1HBAA is required.
b Prewiring between X2M/7+9 and Q1L (= thermal protector backup heater). Do NOT
change.
3 Fix the cable with cable ties to the cable tie mountings.
Wires: (2+1)×0.75 mm²
Maximum load: 0.3 A, 250 V AC
1 Open the following (see
1 Top panel
2 User interface panel
3 Upper switch box cover
2 Connect the space cooling/heating ON/OFF output cable to the appropriate
terminals as shown in the illustration below.
1+2
Wires connected to the alarm output
3
Wire between X2M and A4P
A4P
Installation of EKRP1HBAA is
required.
3
7
7
9
X2M
b
"7.2.4 To open the indoor
9
Electrical installation
|