10
|
Configuration
Power consumption control
Installer reference guide
200
#
Code
[9.8.2]
[D-00]
[9.8.3]
[D-05]
Allowed heaters during preferential kWh rate power supply
Do NOT use 1 or 3.
[D‑00]
0
2
Power consumption control
See
"6  Application
guidelines"  [
functionality.
#
[9.9.1]
[4-08]
[9.9.2]
[4-09]
Limit when [9.9.1]=Continuous and [9.9.2]=Amp:
Allow heater: Which heaters are allowed to
operate during preferential kWh rate power
supply?
0 No: None
1 Only BSH: Booster heater only
2 Only BUH: Backup heater only
3 All: All heaters
See table below.
Setting 2 is only meaningful if the preferential
kWh rate power supply is of type 1 or indoor unit
is connected to a normal kWh rate power supply
(via X2M/5‑6) and the backup heater is NOT
connected to the preferential kWh rate power
supply.
Allow pump:
0 No: Pump is forced off
1 Yes: No limitation
Backup heater
Forced OFF
Allowed
4
  30] for detailed information about this
Code
Power consumption control:
0 No: Disabled.
1 Continuous: Enabled: You can set one
power limitation value (in A or kW) to which
the system power consumption will be
limited for all the time.
2 Inputs: Enabled: You can set up to four
different power limitation values (in A or kW)
to which the system power consumption will
be limited when the corresponding digital
input asks.
Type:
0 Amp: The limitation values are set in A.
1 kW: The limitation values are set in kW.
Description
Compressor
Forced OFF
Description
ERGA04~08EAV3(A) + EHVH04+08SU18+23EA6V
Daikin Altherma 3 R F
4P629090-1 – 2020.08