Technical data
16.5 Table 1 – Maximum refrigerant charge allowed in a room: indoor
unit
Installer reference guide
260
2
A
(m
)
Maximum refrigerant charge in a room (m
room
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
H=600 mm
0.138
0.276
0.414
0.553
0.691
0.829
0.907
0.970
1.028
1.084
1.137
1.187
1.236
1.283
1.328
1.371
1.413
1.454
1.494
1.533
1.571
1.608
1.644
1.679
1.714
1.748
1.781
1.814
1.846
1.877
1.909
ERGA04~08EAV3(A) + EHVH04+08SU18+23EA6V