ERGA04~08EAV3(A) + EHVH04+08SU18+23EA6V
Daikin Altherma 3 R F
4P629090-1 – 2020.08
INFORMATION
Only for systems with integrated domestic hot water tank: If the storage
temperature setpoint is higher than 50°C, Daikin recommends NOT to disable the
backup heater second step because it will have a big impact on the required time for
the unit to heat up the domestic hot water tank.
Capacity step 1
#
Code
[9.3.4]
[6‑03]
Additional capacity step 2
#
Code
[9.3.5]
[6‑04]
Equilibrium
#
Code
[9.3.6]
[5-00]
[9.3.7]
[5-01]
Operation
#
Code
[9.3.8]
[4‑00]
INFORMATION
Only for systems with integrated domestic hot water tank: If backup heater
operation during space heating needs to be limited but can be allowed for domestic
hot water operation, then set [4‑00] to 2.
Description
The capacity of the first step of the backup
heater at nominal voltage.
Description
The capacity difference between the second
and first step of the backup heater at nominal
voltage. Nominal value depends on backup
heater configuration.
Description
Equilibrium: Is backup heater operation
allowed above equilibrium temperature during
space heating operation?
1: NOT allowed
0: Allowed
Equilibrium temperature: Outdoor
temperature below which operation of the
backup heater is allowed.
Range: –15°C~35°C
Description
Backup heater operation:
0: Restricted
1: Allowed
2: Only
DHW Backup heater operation is
enabled for domestic hot water and disabled
for space heating.
10
Configuration
|
Installer reference guide
195