12 Specific data IO-Link (pin 6)
12.4.36 Analog output
The analog output function can be set with the Analog Output parameter.
In-
Sub
Off-
Access
dex
-
set
Rights
In-
dex
0xBA
1
0
R/W
2
8
R/W
3
16
R/W
4
32
R/W
Description of parameter values
Index name
Analog output

12.5 Events

The following IO-Link events can be transmitted.
Device Hardware Fault
Motor Unable To Move
Device Temperature Over-Run
Emergency Power
Primary Supply Voltage Under-Run
Potifail Close
Potifail Open
Description – Events
Event
Device Hardware Fault
0x5000
Motor Unable To Move
0x8CE0
GEMÜ R563
Lengt
Index name
h
Analog output
1 bit
2 bits
16
bits
16
bits
Parameter
Direction
Type
Min.
(0.0% to Max)
Max.
Min to 1000
(Min to 100%)
Event
Description
The event occurs when a
hardware fault is detected.
The event occurs when the
motor is blocked.
Parameter
Direction
Type
Min.
Max.
Values
0
Specify direction of the set value output.
1
0 = Rise (rising)
1 = Fall (falling)
0
Determine signal output.
1
0 = 0 to 20 mA
2
1 = 4 to 20 mA
2 = 0 to 10 V
0 to Max
Determine minimum value of the output.
Determine maximum value of the output.
Mode
App/Disapp
App/Disapp
App/Disapp
App/Disapp
App/Disapp
App/Disapp
App/Disapp
Possible cause
Fault in valve position
detection.
Parameter can no longer be
read when switching the
device on.
Valve is blocked (for example,
solid stuck in valve).
Valve corroded (rusted in
place).
End position can no longer be
reached (after replacing the
diaphragm).
44 / 53
Type
Default
Boolean
0
uint:8
1
uint:16
0
uint:16
1000
Description
Type
Error
Error
Warning/Error
Warning
Error
Warning
Warning
Troubleshooting
Contact GEMÜ Support
Check valve
Carry out initialization if valve
is OK
Values
0
1
0
1
2
0 to Max
(0.0% to Max)
Min to 1000
(Min to 100%)
Code
0x5000
0x8CE0
0x4210
0x5100
0x5111
0x8CA5
0x8CA4
www.gemu-group.com