12.4.14 Function tag
A text with 32 characters can be stored in the device with the Function tag parameter.
For example, installation location, function, installation date, etc.
In-
Sub
Off-
Access
dex
-
set
Rights
In-
dex
0x19
0
0
R/W
12.4.15 Location tag
A text with 32 characters can be stored in the device with the Location tag parameter.
For example, installation location, function, installation date, etc.
In-
Sub
Off-
Access
dex
-
set
Rights
In-
dex
0x1A
0
0
R/W
12.4.16 Device Status
The simple device status can be read out with the Device Status parameter.
In-
Sub
Off-
Access
dex
-
set
Rights
In-
dex
0x24
0
0
RO
Description of parameter values
Index name
Device Status
12.4.17 Detailed Device Status
The detailed device status can be read out with the Detailed Device Status parameter.The values of the array correspond to
the IO-Link events (see chapter 12.5 Events).
In-
Sub
Off-
Access
dex
-
set
Rights
In-
dex
0x25
0
0
RO
Description of parameter values
Index name
Detailed Device Status
www.gemu-group.com
Length
Index name
Function tag
32
bytes
Length
Index name
Location tag
32
bytes
Length
Index name
Device Status
1 byte
Parameter
Values
0
2
4
Length
Index name
Detailed Device
39 byte
Status
Parameter
Values
Parameter
Parameter
Parameter
The valve is operating properly
The valve is operated outside the specification
The valve is in fault status
Parameter
See chapter 12.5 Events
31 / 53
12 Specific data IO-Link (pin 6)
Type
Values
StringT
„**************** "
Type
Values
StringT
„**************** "
Type
Values
uint: 8
0
2
4
Description
Type
Values
ArrayT
See chapter 12.5 Events
Description
GEMÜ R563