12 Specific data IO-Link (pin 6)
In-
Sub-
Access
dex
In-
rights
dex
0x18
0
R/W
0x19
0
R/W
0x1A
0
R/W
0x24
0
RO
0x25
0
RO
0x4B
1
R/W
2
R/W
0x4C
1
R/W
2
R/W
0x4D
0
R/W
0x4E
1
R/W
2
R/W
3
R/W
4
R/W
0x4F
1
R/W
GEMÜ R563
Index name
Application specific
tag
Function tag
Location tag
Device status
Device status
Function digital in-
puts
Function digital in-/
In- / output 1
output 1
Type in- / output 1
Function digital
output 2
Logic digital in-
puts / outputs
Input / output 1
Error action
Parameter
Function
Text with 32 char-
acters can be
entered
Text with 32 char-
acters can be
entered
Text with 32 char-
acters can be
entered
(Simple) device
status
Detailed device
status
Input 1
Configure digital
input 1
Input 2
Configure digital
input 2
Configure digital
inputs/outputs
Configure type of
digital inputs/out-
puts
Configure digital
output
Input 1
Configure logical
digital input 1
Input 2
Configure logical
digital input 2
Configure logical
digital input/out-
Output 2
Configure logical
digital output
Error action
Set safety position
24 / 53
Factory
settings
4
0
2
0
1
0
0
0
put
0
2
Setting options
„****************"
„****************"
„****************"
0 → Operating
properly
2 → Out of
specification
4 → Failure
0 → Off
1 → Open
2 → Close
3 → Safe/On
4 → Init
0 → Off
1 → Open
2 → Close
3 → Safe/On
4 → Init
0 → Output open
1 → Output close
2 → Output error
3 → Output Error &
warning
4 → Input init
0 → Push-pull
1 → NPN
2 → PNP
0 → Output open
1 → Output close
2 → Output error
3 → Output error &
warning
0 → Active high
1 → Active low
0 → Active high
1 → Active low
0 → Active high
1 → Active low
0 → Active high
1 → Active low
0 → Hold
1 → Open
2 → Close
www.gemu-group.com