12.4.35 Set value (W) input
The function of the analog input can be set with the Set value (W) input parameter.
In-
Sub
Off-
Access
dex
-
set
Rights
In-
dex
0xB8
1
0
R/W
2
8
R/W
3
16
R/W
4
24
R/W
5
32
R/W
Description of parameter values
Index name
Set value (W) input
www.gemu-group.com
Lengt
Index name
h
Set value (W) in-
1 bit
put
2 bits
8 bits
8 bits
8 bits
Parameter
Values
Direction
0
1
Type
0
1
2
I min
0 to 40
(0 to 4.0 mA)
I max
200 to 220
(20.0 to 22.0
mA)
U max
100 to 110
(10.0 to 11.0 V)
Parameter
Type
Direction
uint:1
Type
uint:2
I min
uint:8
I max
uint:8
U max
uint:8
Specify direction of the set value input.
0 = Rise (rising)
1 = Fall (falling)
Determine signal input.
0 = 0 to 20 mA
1 = 4 to 20 mA
2 = 0 to 10 V
Determine minimum value of the current input. If the set
value is not reached, the message "Set value too small" is
issued.
Determine maximum value of the current input. If the set
value is exceeded, the message "Set value too high" is
issued.
Determine maximum value of the voltage input. If the set
value is exceeded, the message "Set value too high" is
issued.
43 / 53
12 Specific data IO-Link (pin 6)
Default
Values
0
0
1
1
0
1
2
35
0 to 40
(0 to 4.0 mA)
205
200 to 220
(20.0 to 22.0 mA)
103
100 to 110
(10.0 to 11.0 V)
Description