7 Technical data
Short-circuit proof:
7.7.4 Digital output signals
Outputs:
Type of contact:
Switching voltage:
Switching current:
Short-circuit proof:
7.7.5 Communication
Interface:
Function:
Transmission rate:
Frame type in Operate:
Min. cycle time:
Vendor-ID:
Device-ID:
Product-ID:
ISDU support:
SIO operation:
IO-Link specification:
IODD files can be downloaded via https://ioddfinder.io-link.com/ or www.gemu-group.com.
GEMÜ R563
Yes
Function selectable via IO-Link (see table Overview of available functions – Input and output sig-
nals)
Push-Pull
Power supply Uv
≤ 140 mA
Yes
IO-Link
Parameterization/process data
38400 baud
2.V (eSyStep positioner, code S0),
PDout 3Byte; PDin 3 Byte; OnRequestData 2 Byte
20 ms (eSyStep positioner, code S0)
401
1906801 (eSyStep positioner, code S0),
eSyStep Positioner (code S0)
Yes
Yes
V1.1
12 / 53