12 Specific data IO-Link (pin 6)
12.4.9 Product ID
The product ID can be read out in ASCII format with the Product ID parameter.
In-
Sub
Off-
Access
dex
-
set
Rights
In-
dex
0x13
0
0
RO
12.4.10 Serial number
The serial number of the device can be read out with the Serial number parameter.
The serial number consists of an 8-digit completion confirmation number, a forward slash and a 4-digit index.
In-
Sub
Off-
Access
dex
-
set
Rights
In-
dex
0x15
0
0
RO
12.4.11 Hardware revision
The circuit boards' version can be read out with the Hardware revision parameter.
The hardware version is displayed with the 2-digit version number of the basic assembly and the 2-digit version number of the
OPEN/CLOSED or positioner assembly.
In-
Sub
Off-
Access
dex
-
set
Rights
In-
dex
0x16
0
0
RO
12.4.12 Firmware revision
The software version can be read out with the Firmware revision parameter.
In-
Sub
Off-
Access
dex
-
set
Rights
In-
dex
0x17
0
0
RO
12.4.13 Application specific tag
A text with 32 characters can be stored in the device with the Application specific tag parameter.
For example, installation location, function, installation date, etc.
In-
Sub
Off-
Access
dex
-
set
Rights
In-
dex
0x18
0
0
R/W
GEMÜ R563
Length
Index name
Product ID
18 byte
Length
Index name
Serial number
13
bytes
Length
Index name
Hardware revision
10
bytes
Length
Index name
Firmware revision
21 byte
Length
Index name
Application
32
specific tag
bytes
Parameter
Parameter
Parameter
Parameter
Parameter
30 / 53
Type
Values
StringT
"eSyStep Positioner"
Type
Values
StringT
"XXXXXXXX/YYYY"
Type
Values
StringT
"Rev. XX/XX"
Type
Values
StringT
"V X.X.X.X"
Type
Values
StringT
„**************** "
www.gemu-group.com