Basic Configuration
November 2019
Auto zero
The Auto zero is recommended for optimum performance when a flow meter is initially
installed, and it typically does not need to be performed again. However, if process
conditions drastically change, a new Auto zero is recommended. The sensor must be filled
completely with process fluid at zero flow. For more information, see
5.2

Local operator interface (LOI)

To access the transmitter menu, press the XMTR MENU key. Use the UP, DOWN, LEFT(E),
and RIGHT arrows to navigate the menu structure.
A complete map of the LOI menu structure is shown in
The display can be locked to prevent unintentional configuration changes. The display lock
can be activated through a HART communication device, or by holding the UP arrow for
three seconds and then following the on-screen instructions.
5.3

Other configuration tools

Table 5-1
typical configuration tools.
Table 5-1: Approximate setup category/locations for typical configuration tools
Function
Flow Units
PV Upper Range Value (URV)
PV Lower Range Value (LRV)
Auto zero
Calibration Number
Line Size
Tag
Long Tag
5.4

Measurement units

Table 5-2: Volumetric flow units
gal/sec
L/sec
ft3/sec
m3/sec
42
shows the approximate category or location of basic setup parameters for
Category/Location
Basic Setup
Basic Setup → AO
Basic Setup → AO
Diagnostics
Basic Setup → Setup
Basic Setup → Setup
Device Info → Identification
Device Info → Identification
gal/min
L/min
ft3/min
cm3/min
m3/min
®
Rosemount
LOI Menu
gal/hr
L/hr
ft3/hr
m3/hr
8782 Slurry Magnetic Flow Meter Transmitter with HART Protocol
Reference Manual
00809-0100-8782
Auto
zero.
trees.
gal/day
L/day
ft3/day
m3/day