Installation; Dimensions; Connections - Pepperl+Fuchs VAS-2A1L-K31 Manual

As-interface safety monitor
Table of Contents

Advertisement

5.

Installation

5.1

Dimensions

Warning!
Cover the top of the AS-I Safety Monitor when doing any drilling work above the unit.
No particles, especially metal chips, should be allowed to enter the housing, since this
could cause a short circuit.
Information!
For additional information, please refer to <Section 15 "Appendix: Installation Notes">.
5.2

Connections

5 ... 6 mm / PZ2
10
AWG
Attention!
The AS-I power supply for the AS-I components must have isolation per IEC 60 742
and be able to handle momentary power interruptions of up to 20 ms. The power sup-
ply for the 24 V supply must also have isolation per IEC 60 742 and be able to handle
momentary power interruptions of up to 20 ms. The maximum output voltage of the
power supply must also be less than 42 V in case of a fault.
18
Subject to reasonable modifications due to technical advances.
Pepperl+Fuchs Group · Tel.: Germany (6 21) 7 76-0 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91
85
0,8 Nm
7 LB.IN
10
2 x (0,5 ... 1,5) mm
2 x (0,5 ... 1,5) mm
2 x 24 ...12
AS-i Safety Monitor for 2 AS-i circuits
96
2
2
Installation
120
© Pepperl+Fuchs, Printed in Germany
Internet http://www.pepperl-fuchs.com