Configure the AS-i Safety Monitor and start it up as described in the software
manual.
Attention!
Before starting up the device you must adapt the device configuration to your
application. This means configuring the AS-i Safety Monitor according to the soft-
ware manual so that the location to be protected is in fact protected by the device.
8.3.2

Description of configuration using chip card with master configuration

Generating a master configuration:
Generate a configuration using the ASIMON 3 G2 software
Load the configuration into the device
Release (validate) the configuration, but do not teach the code sequences
The code sequences will be taught on the physical AS-i circuit
Attention!
Safety advisory:
Ensure that the chip card contains the configuration intended for and released for
the application!
This can be done by comparing the release codes on the display (section MONI-
TOR CONFIG (configuration of the int. monitor)):
The safety representative who generated and validated the release code
stores the release code for the master configuration and approves use of the
configuration for specific equipment.
The person performing the startup reads out the release code on the display
before teaching the code and compares it with the release code stored and
approved for the equipment.
After the chip card has been used to load the configuration into the device, the
safety functions of the device must be checked in the equipment.
Checking of the release code and testing the system must be documented in wri-
ting and is part of the system documentation.
8.3.3

Configuration using a chip card with complete configuration

The chip card contains the complete configuration if:
An empty chip cared is plugged into an AS-i Safety Monitor which already
contains a complete configuration, or
44
Subject to reasonable modifications due to technical advances.
Pepperl+Fuchs Group · Tel.: Germany (6 21) 7 76-0 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91
To connect, plug the diagnostic cable end with the PS2 connector into
the socket of the diagnostic interface (RS 232) of the monitor and the
other end with the 9-pin Sub-D socket connector to a free COM port
(serial RS232 interface) on your PC (see section "Connection bet-
ween the AS-i Safety Monitor and the PC" in the software manual).
AS-i Safety Monitor for 2 AS-i circuits
Function and startup of the Safety Monitor
© Pepperl+Fuchs, Printed in Germany
Internet http://www.pepperl-fuchs.com