Fieldbus connection valve terminals type 03/05
Hide thumbs Also See for FB13:
Table of Contents

Advertisement

VIFB13 - 03/05
3.2.2 Type 05: Connecting the operating voltages
3-22
3. Installation
WARNING
Use only power units which guarantee reliable
isolation of the operating voltages as per IEC
742/EN 60742/VDE 0551 with at least 4 kV
isolation resistance (protected extra low volt-
age, PELV). Switch power packs are permitted
if they guarantee reliable isolation in accord-
ance with EN 60950/VDE 0805.
Remark:
By using PELV power units, protection against
electric shock (protection against direct and
indirect contact) in accordance with EN 60204-1/
IEC 204 is guaranteed on Festo valve terminals.
Safety transformers with the adjacent designa-
tion must be used for supplying PELV networks.
The valve terminals must be earthed in order to
ensure their function (e.g. EMC).
CAUTION
The power supply to the outputs/valves (pin 2)
must be separately fused externally with max.
10 A. The external fuse prevents the valve ter-
minal from being damaged in the event of a
short circuit.
9809b