Festo FB13 Electronic Manual page 157

Fieldbus connection valve terminals type 03/05
Hide thumbs Also See for FB13:
Table of Contents

Advertisement

VIFB13 - 03/05
Octet 5 and 6: Ident_Number
Octet 7: Ext_Diag_Data (device-related diagnosis)
Octet 8: Device-related diagnosis 1
Bit
Meaning
Error ASI
0
(bus error)
1
Error ASI
(nominal- <> actual
configuration)
Short circuit/overload
2
electrical outputs
3
Error ASI (power fail)
4
V
sen
5
V
val
6
V
out
Error analogue
7
*) only if voltage monitoring is activated (see Chapter 3.2, DIL switch)
9809b
5. Diagnosis/error treatment
Manufacturer identifier
Explanation
These octets contain the manufacturer identifier:
FB09
for the Festo valve terminal types 03-05.
H
Header device-related diagnosis
Explanation
This octet represents the header for the
device diagnosis.
The valve terminal enters the value 8 in this
octet, i.e. 8 octets for device-related diagnosis
are transferred (incl. header octet). This value is
independent of the extent to which the valve ter-
minal is fitted with valves or other modules such
as analogue modules or AS-i master.
Structure of device-related diagnosis 1
Explanation
Logic "1":
error in AS-i bus
Logic "1":
AS-i nominal configuration does not correspond
to AS-i actual configuration
Logic "1": At least one electrical output short
circuited or overloaded. The faulty output can be
localized more closely with the "Device-related
diagnosis" 2 and 3.
Logic "1": AS-i supply voltage outside of tolerances
Voltage supply for sensors <10 V
Voltage supply for valve coils <21.6 V
Voltage supply for valve coils and
electrical outputs <10 V
Logic "1":
Short circuit of an analogue voltage input
or hardware error on analogue module
*)
5-23