3. Installation
Power unit
PLEASE NOTE
Please note that with a common voltage sup-
ply for pin 1 (electronic components and in-
puts) and pin 2 (outputs/valves), the lower
tolerance of ± 10 % for both circuits must be
observed.
Check the 24 V operating voltage of the outputs
while your system is operating. Make sure that
the operating voltage of the outputs lies within
the permitted tolerances even during full oper-
ation.
Recommendation
Use a closed loop power unit.
Calculate the complete current consumption
according to the following table and select
both a suitable power unit and cable sectional
area.
Avoid long distances between the power unit
and the terminal. Calculate the permitted
distance according to Appendix A.
The following rule applies for type 03:
Operating
Cable sectional
voltage
area
Pin 1
= 2.2 A
Pin 2
= 10 A
V
= 24 V
B
Distance
≤ 8 m
2
1.5 mm
2
≤ 14 m
2.5 mm
3-17