System data
Number of I/O modules
Number of I/O points
Data transfer medium
Segment length
Number of segments
Data transfer rate
Topology
Transmission time
2.3.3

Technical Data - PLC

PLC data
Programmability
Program memory
Source code memory
Data memory
Remanent flags
PLC cycle time
Programming languages
Runtime
Online Change
Up/Down Load Code
12
PROFIBUS (BC3150)
126 (BC3150 max. 99 devices)
depending on controller
shielded copper cable 2 x 0.25 mm², cable type A according to
EN 50 170
up to 1200 m
3
up to 12 MBaud
RS485 line, optical fiber ring
approx. 0.5 ms with 10 stations for 32 bits input/output at 12 MBaud
BCxx5x
via serial programming interface or via the fieldbus
48 kbyte
128 kbyte
32 kbyte
2 kbyte
Approx. 3.0 ms for 1000 IL commands (without I/O cycle)
IEC 6-1131-3 (IL, LD, FBD, ST, SFC)
1 PLC task
Yes
Yes/Yes