Ads Connection Via Serial Interface; Fig. 29 Other Memory - Beckhoff BC3150 Documentation

Bus terminal controller for profibus-dp
Table of Contents

Advertisement

Fig. 29: Other memory
4.2.6

ADS connection via serial interface

(from firmware version 1.xx or 0.99x, Bus Terminal Controllers of the BX series and for all BCxx50)
From TwinCAT 2.9 build 1020 (TwnCAT level PLC, NC or NCI)
Use only a serial connection
To ensure trouble-free operation of the ADS link via the serial interface, only a serial con-
nection to the BX controller is allowed.
Note
After successful configuration via the System Manager, close the System Manager before
starting programming.
AMS Net ID in delivery state (default)
For BX9000
The default AMS Net ID is 172.16.21.20.1.1. If the IP address of the BX9000 is changed,
Note
the AMS Net ID of the BX9000 also changes. There is a menu option for displaying the cur-
rent AMS Net ID.
Example: If you change the IP address to 10.2.3.7, the AMS Net ID changes to
10.2.3.7.1.1.
For BC9050, BC9020, BC9120
The default AMS Net ID is 172.16.xxx.[DIP switch].1.1. If the IP address of the BX9xxx is
changed, the AMS Net ID of the BX9xxx also changes.
Example: If you change the IP address to 10.2.3.7, the AMS Net ID changes to
10.2.3.7.1.1.
BC9050: DEFAULT 172.16.21.[DIP-Switch].1.1
BC9020: DEFAULT 172.16.22.[DIP-Switch].1.1
BC9120: DEFAULT 172.16.23.[DIP-Switch].1.1
Initializing the ADS connection
Enter the Bus Terminal Controller in the remote connection under TwinCAT. Click on the TwinCAT icon and
open the features menu. The following settings can be made under the >AMS Remote< tab.
BC3150
Version: 2.1.0
Parameterization and Commissioning
35

Advertisement

Table of Contents
loading

Table of Contents