Description of the controller functions

7.2 Delayed outdoor temperature adaptation

Set the function block F3 to 1 = ON and P7 = Delayed outdoor temperature adaptation
A sensor AS for the outdoor temperature is required.
This function accounts for the fact that a building stores heat. Usually, short-term variations
in outdoor temperature do not affect the room temperature.
The function makes sure that brief variations in outdoor temperature (e.g. warm winds) are
not included in the flow temperature control.
If the outdoor temperature changes rapidly, this change is only taken into account to a cer-
tain degree. The change in outdoor temperature that is taken into account in the control is
defined over the parameter P7 (Delayed outdoor temperature adaptation).
For example, if the outdoor temperature changes by 7 °C/hr, just a 5 °C/hr change is used
for the control. This means, the calculated outdoor temperature changes more slowly than
the measured outdoor temperature. This function also applies when the controller switches
over to summer time operation.
The parameter P7 can be set in the range from 1 to 6 °C/hr. The setting of this parameter
depends on personal preferences and the building characteristic. The default setting is
5 °C/hr.

7.3 Control signal

This setting determines whether the control signal is a three-step signal or on/off signal.

7.3.1 Three-step control

Set F4 to 1 = ON and P10 = Kp Gain, P11 = Tn Reset time and P12 = Ty Actuator transit
time.
The function of the three-step control has proportional plus integral action (PI controller).
Over the parameters P10 (gain factor Kp) and P11 (reset time Tn) the behavior of the control
loop can be influenced.
With the aid of parameter P12, the transit time of the control valve (Ty) is taken into account
in the algorithms. The control signal issuing is limited to three times of the duration of the con-
trol valve transit time (3 x Ty).
Note: If Tn = 0 is set, the controller functions only as a P controller.
25
EB 5432-1 EN