Setting The Function Blocks And Parameters - Samson TROVIS 5432 Mounting And Operating Instructions

Heating and district heating controller for automation system trovis 5400
Hide thumbs Also See for TROVIS 5432:
Table of Contents

Advertisement

Configuration and parameterization

6.2 Setting the function blocks and parameters

Note: When you set certain function blocks, the associated parameter needs to be set, too.
The function blocks (F) and parameters (P) are listed in sequence. Further details about the
functions are described in chapter 7.
F
P
Function
F= Function block
F 1
Operating mode
P1
Gradient Heat. characteristic
P2
Level Heating characteristic
F 2
Manual operation
F 3
Delayed outdoor
temperature adaptation
P7
F 4
Control signal 3-step
P10 Kp Gain
P11 Tn Reset time
P12 Ty Valve transit time
Control signal on/off
P13 Differential gap
P14 Minimum activation time
P15 Minimum deactivation time
F 5
Automatic clock reset
summer time/winter time
F 6
Subfloor drying
20
EB 5432-1 EN
S
P= Parameter
S = Setting
1
0
1.6
0.0
1
0
1
0
1
2.0
120 0...999 s
0
120 0...600 s
120
1
0
1
0
FS
Comment / range
FS = Factory (default) settings
1
Weather-compensated control
Fixed set point control
0.2...3.2
-30.0...30.0 °C
Active
0
Not active
Active with outdoor sensor AS
0
5
1....6 °C/hr
1
Three-step control
0.1...50.0
45
10...240 s
On/off control
5
2...10 °C
0...600 s
1
Active
Not active
Active
0
Not active
(Chap. 7.1)
(Chap. 7.10)
(Chap. 7.2)
(Chap. 7.3.1)
(Chap. 7.3.2)
(Chap. 7.7)