Configuration A; Applications - ABB RELION 611 Series Applications Manual

Busbar and multipurpose differential protection and control
Hide thumbs Also See for RELION 611 Series:
Table of Contents

Advertisement

1MRS757455 E
3.4
3.4.1
REB611
Application Manual
L1
L2
L3
G
3~
GUID-00968A99-E6A2-4649-A50F-28E52CB8F484 V1 EN
Figure 14:
Connection diagram for configuration A when used as rotating
machine restricted earth-fault protection

Configuration A

Applications

Configuration A for phase-segregated high-impedance differential protection and
non-directional earth-fault protection is mainly intended for use in high-impedance-
based applications within utility substations and industrial power systems. In addition,
the protection relay can also be used in restricted earth-fault and residual earth-fault
applications for the protection of generators, motors, transformers and reactors.
The protection relay with a standardized configuration is delivered from the factory
with default settings and parameters. The end-user flexibility for incoming, outgoing
and internal signal designation within the protection relay enables this configuration
to be further adapted to different primary circuit layouts and the related functionality
needs by modifying the internal functionality using PCM600.
REB611 standardized configuration
X120
1
BI 1
2
3
BI 2
4
BI 3
Ru
Rs
5
BI 4
6
1)
7
1/5A
IL1
8
N
9
1/5A
IL2
10
N
11
1/5A
IL3
12
N
13
1/5A
Io
14
N
Section 3
REB611
+
U
aux
-
IRF
PO1
PO2
SO1
SO2
PO3
TCS1
PO4
TCS2
1) The IED features an automatic short-circuit
mechanism in the CT connector when plug-in
unit is detached
X100
1
2
3
4
5
6
7
8
9
10
11
12
13
14
16
17
15
19
18
20
22
21
23
24
31