Section 3
REB611 standardized configuration
38
Channel number
Binary channel 12
Binary channel 13
Binary channel 14
Binary channel 15
Binary channel 16
Binary channel 17
Binary channel 18
Binary channel 19
Binary channel 20
Binary channel 21
Binary channel 22
SELGAPC1
IN_3
OUT_3
X120-BI3
CB Open Position
OR
TRPPTRC1_TRIP
TRPPTRC2_TRIP
GUID-535EAC11-8657-4F5B-BAB2-E91FF795C817 V2 EN
Figure 21:
Trip circuit supervision
Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3
(X100:15-19) and TCSSCBR2 for PO4 (X100:20-24). Both functions are blocked by
the master trip (TRPPTRC1 and TRPPTRC2) and the circuit breaker open position.
The TCS alarm indication is connected to LED 7.
Channel id text
CCBRBRF1_TRBU
HZCCASPVC1_ALARM
HZCCBSPVC1_ALARM
HZCCCSPVC1_ALARM
SELGAPC1_External Trip
SG_1_ACT
SG_2_ACT
SG_3_ACT
SG_4_ACT
SG_5_ACT
SG_6_ACT
TRIP CIRCUIT SUPERVISION
SELGAPC2
TCSSCBR1
OUT_1
BLOCK
IN_2
OUT_2
TCSSCBR2
BLOCK
1MRS757455 E
Level trigger mode
4=level trigger off
1=positive or rising
1=positive or rising
1=positive or rising
4=level trigger off
4=level trigger off
4=level trigger off
4=level trigger off
4=level trigger off
4=level trigger off
4=level trigger off
OSWGAPC13
SELGAPC4
IN_5
ALARM
IN_15
OUT
OR
IN_6
ALARM