Section 3
REB611 standardized configuration
44
OSWGAPC3 to OSWGAPC6 are used for the start signal. The inputs are start
signals from the protection functions.
OSWGAPC7 to OSWGAPC10 are used for the trip signal. The inputs are
operation signals from the protection functions.
OSWGAPC11 to OSWGAPC16 are used for the alarm signal. The inputs are
alarm signals from the protection and monitoring functions.
OSWGAPC1
HIAPDIF1_OPERATE
HIBPDIF1_OPERATE
HICPDIF1_OPERATE
EFLPTOC1_OPERATE
EFHPTOC1_OPERATE
OSWGAPC2
CCBRBRF1_TRRET
OSWGAPC3
OSWGAPC4
HIAPDIF1_START
HIBPDIF1_START
HICPDIF1_START
EFLPTOC1_START
EFHPTOC1_START
OSWGAPC5
OSWGAPC6
OSWGAPC7
OSWGAPC8
HIAPDIF1_OPERATE
HIBPDIF1_OPERATE
HICPDIF1_OPERATE
EFLPTOC1_OPERATE
EFHPTOC1_OPERATE
OSWGAPC9
OSWGAPC10
OSWGAPC11
OSWGAPC12
HZCCASPVC1_ALARM
HZCCBSPVC1_ALARM
HZCCCSPVC1_ALARM
RDRE_TRIGGERED
OSWGAPC13
TCSSCBR1_ALARM
TCSSCBR2_ALARM
CCBRBRF1_TRBU
OSWGAPC14
CCBRBRF1_TRRET
SELGAPC1_OUT_6
TRPPTRC1_CL_LKOUT
TRPPTRC2_CL_LKOUT
OSWGAPC15
OSWGAPC16
GUID-9968F50A-8710-4EF7-A980-78A82488B59D V2 EN
Figure 31:
Binary outputs
Master Trip 1
TRPPTRC1
Master Trip 2
TRPPTRC2
TPGAPC1
Start 1
IN1
OUT1
Start 2
IN2
OUT2
TPGAPC2
Start 3
IN1
OUT1
Start 4
IN2
OUT2
TPGAPC3
Trip 1
IN1
OUT1
Trip 2
IN2
OUT2
TPGAPC4
Trip 3
IN1
OUT1
Trip 4
IN2
OUT2
TPGAPC5
Alarm 1
IN1
OUT1
Alarm 2
IN2
OUT2
TPGAPC6
Alarm 3
IN1
OUT1
Alarm 4
IN2
OUT2
TPGAPC7
Alarm 5
IN1
OUT1
Alarm 6
IN2
OUT2
1MRS757455 E
X100 PO1
X100 PO2
X100 SO1
X100 SO2
SELGAPC3
X100 PO3
X100 PO4
REB611
Application Manual