ABB RELION 611 Series Applications Manual page 42

Busbar and multipurpose differential protection and control
Hide thumbs Also See for RELION 611 Series:
Table of Contents

Advertisement

Section 3
REB611 standardized configuration
36
GUID-A45C3D99-3B0D-48D9-B152-6BEEBBC29A82 V2 EN
Figure 18:
Earth-fault protection
Two stages are offered for non-directional earth-fault protection. The operate signals
of the earth-fault protections are connected to the Master Trip.
HIAPDIF1_OPERATE
HIBPDIF1_OPERATE
OR
HICPDIF1_OPERATE
EFLPTOC1_OPERATE
EFHPTOC1_OPERATE
SELGAPC1
IN_2
OUT_2
X120-BI2
CB Closed Position
GUID-03078895-719E-4704-84A7-EDFFBE60DD4A V2 EN
Figure 19:
Circuit breaker failure protection
The circuit-breaker failure protection CCBRBRF1 is initiated via the start input by a
number of different protection stages in the protection relay. CCBRBRF1 offers
different operating modes associated with the circuit breaker position and the
measured phase and residual currents. CCBRBRF1 has two operating outputs:
TRRET and TRBU. The TRRET operate output is used for retripping its own circuit
breaker through Master Trip 2. The TRBU output is used to give a backup trip to the
EARTH-FAULT PROTECTION
EFLPTOC1
I
>(1)
0
51N-1(1)
I
OPERATE
0
BLOCK
START
ENA_MULT
EFHPTOC1
I
>>(1)
0
51N-2(1)
I
OPERATE
0
BLOCK
START
ENA_MULT
CIRCUIT BREAKER FAILURE PROTECTION
CCBRBRF1
3I>/I
>BF(1)
0
51BF/51NBF(1)
3I
CB_FAULT_AL
I
TRBU
0
TRRET
START
POSCLOSE
CB_FAULT
BLOCK
1MRS757455 E
SELGAPC3
IN_4
OUT_2
X100 PO2
OSWGAPC14
SELGAPC4
OUT_8
IN_7
OUT
IN_16
Application Manual
LED 8
REB611