Functional Diagrams For Disturbance Recorder - ABB RELION 611 Series Applications Manual

Busbar and multipurpose differential protection and control
Hide thumbs Also See for RELION 611 Series:
Table of Contents

Advertisement

1MRS757455 E
3.4.3.2
REB611
Application Manual
circuit-breaker feeding upstream. For this purpose, the TRBU operate output signal is
connected to the output PO2 (X100:8-9). LED 8 is used for backup (TRBU) operate
indication.

Functional diagrams for disturbance recorder

HIAPDIF1_OPERATE
HIBPDIF1_OPERATE
OR
HICPDIF1_OPERATE
EFLPTOC1_OPERATE
OR
EFHPTOC1_OPERATE
SELGAPC1_ CB Closed Position
SELGAPC1_ CB Open Position
HZCCASPVC1_ALARM
HZCCBSPVC1_ALARM
HZCCCSPVC1_ALARM
SELGAPC1_External Trip
GUID-76A45579-A1D9-4048-8A86-BB2AFC0CE8C7 V2 EN
Figure 20:
Disturbance recorder
All start and operate signals from the protection stages are routed to trigger the
disturbance recorder or alternatively only to be recorded by the disturbance recorder
depending on the parameter settings. Additionally, the selected autoreclosing output
signals and the three binary inputs from X120 are also connected. The active setting
group is also to be recorded via SG_1_ACT to SG_6_ACT. The disturbance recorder
triggered signal indication is connected to LED 6.
Table 15:
Disturbance recorder binary channel default value
Channel number
Binary channel 1
Binary channel 2
Binary channel 3
Binary channel 4
Binary channel 5
Binary channel 6
Binary channel 7
Binary channel 8
Binary channel 9
Binary channel 10
Binary channel 11
Table continues on next page
REB611 standardized configuration
DISTURBANCE RECORDER
RDRE1
HIAPDIF1_START
TRIGGERED
C1
HIBPDIF1_START
C2
HICPDIF1_START
C3
EFLPTOC1_START
C4
EFHPTOC1_START
C5
C6
C7
SELGAPC1_ Blocking
C8
C9
C10
CCBRBRF1_TRRET
C11
CCBRBRF1_TRBU
C12
C13
C14
C15
C16
SG_1_ACT
C17
SG_2_ACT
C18
SG_3_ACT
C19
SG_4_ACT
C20
SG_5_ACT
C21
SG_6_ACT
C22
Channel id text
HIAPDIF1_START
HIBPDIF1_START
HICPDIF1_START
EFLPTOC1_START
EFHPTOC1_START
HIxPDIF1_OPERATE
EFxPTOC1_OPERATE
SELGAPC1_Blocking
SELGAPC1_CB_Closed
SELGAPC1_CB_Open
CCBRBRF1_TRRET
Section 3
OSWGAPC12
SELGAPC4
IN_4
IN_14
OUT
OUT_6
Level trigger mode
1=positive or rising
1=positive or rising
1=positive or rising
1=positive or rising
1=positive or rising
4=level trigger off
4=level trigger off
4=level trigger off
4=level trigger off
4=level trigger off
4=level trigger off
LED 6