Functions - ABB RELION 611 Series Applications Manual

Busbar and multipurpose differential protection and control
Hide thumbs Also See for RELION 611 Series:
Table of Contents

Advertisement

Section 3
REB611 standardized configuration
3.4.2
Io
3I
3I
GUID-57FB15B3-447A-4D9D-B342-C01EDA83D3F0 V1 EN
Figure 15:
Functionality overview for configuration A
32
Breaker control CBXCBR and breaker failure protection CCBRBRF are always
associated with one set of phase current inputs. In REB611, the current inputs are
phase differential currents, that is, a vector-sum of all phase feeder currents that flow
in or out of the same bus. The bus differential current is not a feeder phase current and
is normally zero. If a bus fault occurs and any phase differential protection picks up,
all breakers that connect to the bus should be tripped.
As there is only one set of breaker control and breaker failure protection, and multiple
breakers are associated with the bus protection especially when multiple source
feeders are connected to the bus, these functions must be dealt with application-
specifically.
Since the differential current cannot simply reflect any source breaker, the breaker
control and breaker failure protection should be turned off.

Functions

REB611
BUSBAR AND MULTIPURPOSE DIFFERENTIAL PROTECTION RELAY
PROTECTION
Master Trip
Lockout relay
94/86
3I>/Io>BF
Io>
51BF/51NBF
51N-1
∆3I
dHi>
87
LOCAL HMI
A
Control
Events
Measurements
Disturbance records
I
ESC
O
Io>>
51N-2
CONDITION MONITORING
AND SUPERVISION
MCS 1I
TCS
MCS 1I
TCM
CONTROL AND INDICATION
Object
CB
DC
ES
Check availability of binary inputs/outputs
1)
from technical documentation
Control and indication function for
2)
primary object
Status indication function for
3)
primary object
REMARKS
Optional
function
1MRS757455 E
STANDARD
CONFIGURATION
ALSO AVAILABLE
- Disturbance and fault recorders
- Event log and recorded data
- Local/Remote push button on LHMI
- Self-supervision
- Time synchronization: IEEE 1588 v2,
SNTP, IRIG-B
- User management
- Web-HMI
R
L
COMMUNICATION
Protocols:
IEC 61850-8-1
Modbus®
Interfaces:
Ethernet: TX (RJ-45), FX (LC)
Serial:
RS-485
Redundant protocols:
HSR
PRP
RSTP
MEASUREMENT
1)
- 3I, Io
Ctrl
Ind
2)
3)
- Limit value supervision
- Symmetrical components
1
-
-
-
Analog interface types
-
-
Current transformer
Voltage transformer
Conventional transformer inputs
1)
No. of
Calculated
Alternative
OR
instances
value
function to be
Io/Uo
defined when
ordering
Application Manual