1MRS757455 E
REB611
Application Manual
Three high-impedance differential protection instances are offered. By default,
HIAPDIF1 is for phase A current channel, HIBPDIF1 is for phase B current channel,
and HICPDIF1 is for phase C current channel. The ALARM outputs of the phase-
segregated current transformer supervision HZCCxSPVC block HIxPDIF.
HIAPDIF1 operate signal is connected to LED 1, HIBPDIF1 operate signal is
connected to LED 2, HICPDIF1 operate signal is connected to LED 3. All the start
signals from HIAPDIF1, HIBPDIF1 and HICPDIF1 are connected to LED 4.
HZCCASPVC1
MCS 1I(1)
MCS 1I(1)
I_A
BLOCK
HZCCBSPVC1
MCS 1I(2)
MCS 1I(2)
I_B
BLOCK
HZCCCSPVC1
MCS 1I(3)
MCS 1I(3)
I_C
BLOCK
GUID-2777A166-E375-4BC4-90D7-87A80E477393 V2 EN
Figure 17:
Phase segregated CT supervision
Three phase-segregated current transformer supervision instances are offered. By
default, HZCCASPVC1 is for phase A current channel, HZCCBSPVC1 is for phase
B current channel, and HZCCCSPVC1 is for phase C current channel.
All the ALARM output signals are connected to LED 5.
REB611 standardized configuration
PHASE SEGREGATED CT SUPERVISION
ALARM
OSWGAPC11
IN_1
IN_2
ALARM
IN_3
ALARM
Section 3
SELGAPC4
OUT
IN_13
OUT_5
OR
LED 5
35