Section 3
REB611 standardized configuration
42
SELGAPC1
SELGAPC1 has inputs from protection relay binary inputs. IN_1 to IN_4 are binary
inputs from X120. An always true signal is connected to IN_5. SELGAPC1 outputs
are used to route inputs to different functions. By setting SELGAPC1, binary inputs
can be configured for different purposes.
X120/1-2 BI1
X120-BI1
IN_1
X120/3-2 BI2
X120-BI2
IN_2
X120/4-2 BI3
X120-BI3
IN_3
X120/5-6 BI4
X120-BI4
IN_4
IN_5
Always True
GUID-C41611AC-B385-438D-AF2F-DACEC6B69B48 V1 EN
Figure 27:
SELGAPC1
ISWGAPC1
ISWGAPC1 is used to select which protection functions are to be blocked by changing
ISWGAPC1 parameters. ISWGAPC1 input is routed from SELGAPC1 output
OUT_1 Blocking 1. ISWGAPC1 outputs are connected to the BLOCK inputs of
the protection functions.
Blocking 1
GUID-404D31F7-C132-46B4-8AFA-321C80881FA3 V2 EN
Figure 28:
ISWGAPC1
SELGAPC1
Blocking 1
OUT_1
CB Closed Position
OUT_2
CB Open Position
OUT_3
CB Close Enable
OUT_4
TRPTTRC1/2_
RST_LKOUT
OUT_5
External Trip
OUT_6
Setting Group 2
OUT_7
Setting Group 3
OUT_8
Setting Group 4
OUT_9
ISWGAPC1
OUT_1
OUT_2
OUT_3
OUT_4
IN
OUT_5
OUT_6
OUT_7
OUT_8
1MRS757455 E
ISWGAPC1_IN
CBXCBR1_POSCLOSE
SELGAPC2_IN_1
CBXCBR1_POSOPEN
SELGAPC2_IN_2
CBXCBR1_ENA_CLOSE
TRPTTRC1_RST_LKOUT
TRPTTRC2_RST_LKOUT
TRPTTRC1_OPERATE
TRPTTRC2_OPERATE
PROTECTION_BI_SG_2
PROTECTION_BI_SG_3
PROTECTION_BI_SG_4
HIAPDIF1_BLOCK
HIBPDIF1_BLOCK
HICPDIF1_BLOCK
EFLPTOC1_BLOCK
EFHPTOC1_BLOCK
HZCCASPVC1_BLOCK
HZCCBSPVC1_BLOCK
HZCCCSPVC1_BLOCK
Application Manual
REB611