ABB RELION 611 Series Applications Manual page 57

Busbar and multipurpose differential protection and control
Hide thumbs Also See for RELION 611 Series:
Table of Contents

Advertisement

1MRS757455 E
REB611
Application Manual
HIAPDIF1_OPERATE
HIBPDIF1_OPERATE
HICPDIF1_OPERATE
EFLPTOC1_OPERATE
EFHPTOC1_OPERATE
GUID-AB3796EF-B15B-4007-B4CA-FD7CEA0C111A V2 EN
Figure 44:
OSWGAPC10
Alarm OSWGAPCs
OSWGAPC instances 11...16 are used to configure the alarm signals that belong to the
alarm group. These six OSWGAPCs have the same inputs from the alarm signals. The
output is routed to SELGAPC3 via TPGAPC timer and to SELGAPC4 directly.
HZCCASPVC1_ALARM
HZCCBSPVC1_ALARM
HZCCCSPVC1_ALARM
RDRE_TRIGGERED
TCSSCBR1_ALARM
CCBRBRF1_TRBU
CCBRBRF1_TRRET
SELGAPC1_OUT_6
TRPPTRC1_CL_LKOUT
TRPPTRC2_CL_LKOUT
GUID-5ADF1ED1-B09A-45E0-9CBB-B51884694F25 V2 EN
Figure 45:
OSWGAPC11
REB611 standardized configuration
OSWGAPC10
IN_1
IN_2
Trip 4
IN_3
OUT
IN_4
IN_5
OSWGAPC11
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
External Trip
IN_9
IN_10
IN_11
Section 3
TPGAPC4_IN2
SELGAPC4_IN_12
TPGAPC5_IN1
Alarm 1
OUT
SELGAPC4_IN_13
51