1MRS757455 E
REB611
Application Manual
GOOSERCV_BIN:0
GOOSERCV_BIN:1
GOOSERCV_BIN:2
GOOSERCV_BIN:3
GOOSERCV_BIN:4
GOOSERCV_BIN:5
GOOSERCV_BIN:19
GUID-F0B9A987-3F7E-4180-BA29-99A3F602B38E V2 EN
Figure 51:
GOOSE overview
ISWGAPC9
ISWGAPC9 is used to configure which protection functions can be blocked by the
received GOOSE signals. ISWGAPC9 inputs are received GOOSE signals from
GOOSERCV_BIN:0 and GOOSERCV_BIN:1. The outputs are connected to the
block inputs of the protection functions.
GOOSE Blocking
GUID-C0121EA1-DD3D-428C-BEB9-2B7613F1DC46 V2 EN
Figure 52:
ISWGAPC9
REB611 standardized configuration
GOOSE Blcoking
ISWGAPC9
OR
GOOSE
External Trip
OR
GOOSE Block CB
OR
ISWGAPC10
ISWGAPC9
OUT_1
OUT_2
OUT_3
OUT_4
IN
OUT_5
OUT_6
OUT_7
OUT_8
Section 3
HIAPDIF1_BLOCK
HIBPDIF1_BLOCK
HICPDIF1_BLOCK
EFLPTOC1_BLOCK
EFHPTOC1_BLOCK
HZCCASPVC1_BLOCK
HZCCBSPVC1_BLOCK
HZCCCSPVC1_BLOCK
CBXCBR1_BLK_CLOSE
CBXCBR1_BLK_OPEN
HIAPDIF1_BLOCK
HIBPDIF1_BLOCK
HICPDIF1_BLOCK
EFLPTOC1_BLOCK
EFHPTOC1_BLOCK
HZCCASPVC1_BLOCK
HZCCBSPVC1_BLOCK
HZCCCSPVC1_BLOCK
55