Operation Functionality; Optional Functions; Physical Hardware - ABB RELION 611 Series Applications Manual

Busbar and multipurpose differential protection and control
Hide thumbs Also See for RELION 611 Series:
Table of Contents

Advertisement

1MRS757455 E
2.2
2.2.1
2.3
REB611
Application Manual

Operation functionality

Optional functions

Modbus TCP/IP or RTU/ASCII
IEEE 1588 time v2 synchronization
High-availability seamless redundancy protocol (HSR)
Parallel redundancy protocol (PRP)

Physical hardware

The protection relay consists of two main parts: plug-in unit and case. The content
depends on the ordered functionality.
Table 2:
Plug-in unit and case
Main unit
Slot ID
Content options
Plug-in
-
HMI
unit
X100
Auxiliary
power/BO module
X120
AI/BI module
Case
X000
Optional
communication
module
1) The 0.2/1 A input is normally used in applications requiring sensitive earth-fault protection and featuring
core-balance current transformers.
Rated values of the current and voltage inputs are basic setting parameters of the
protection relay. The binary input thresholds are selectable within the range 16...176
V DC by adjusting the binary input setting parameters.
See the installation manual for more information about the case and
the plug-in unit.
The connection diagrams of different hardware modules are presented in this manual.
Table 3:
Number of physical connections in configuration
Conf.
Analog channels
CT
A
4
Small (4 lines, 16 characters)
48...250 V DC/100...240 V AC; or 24...60 V DC
2 normally-open PO contacts
1 change-over SO contacts
1 normally-open SO contact
2 double-pole PO contacts with TCS
1 dedicated internal fault output contact
Configuration A:
3 differential phase current inputs (1/5 A)
1 residual current input (1/5 A or 0.2/1 A)
4 binary inputs
See technical manual for details about different type of
communication modules.
Binary channels
VT
BI
-
4
Section 2
REB611 overview
1)
BO
6
11