Clearing of record

The load profile record can be cleared with Reset load profile rec via HMI,
communication or the ACT input in PCM600. Clearing of the record is allowed only on
the engineer and administrator authorization levels.
The load profile record is automatically cleared if the quantity selection parameters are
changed or any other parameter which affects the content of the COMTRADE
configuration file is changed. Also, if data source for selected quantity is removed, for
example, with ACT, the load profile recorder stops recording and previously collected
data are cleared.

Configuration

The load profile record can be configured with the PCM600 tool or any tool supporting the
IEC 61850 standard.
The load profile record can be enabled or disabled with the Operation setting under the
Configuration/Load Profile Record menu.
The recording buffer is filled in FIFO manner, meaning that oldest data is overwritten by
newest data. If oldest data is considered important, Mem. warning level and Mem. alarm
10
.
187
L D P 1
0 A
B B
L D P 1 . C F G
0 A
B B
L D P 1 . D A T
Section 3
Basic functions
107