5 Installation and Wiring
5-3-1

Installation in a Control Panel

Installation in Cabinets or Control Panels
When the NX-series Controller is being installed in a cabinet or control panel, be sure to provide prop-
er ambient conditions as well as access for operation and maintenance.
l Temperature Control
The ambient temperature within the NX-series Controller must be within the operating range of 0 to
55°C. When necessary, take the following steps to maintain the proper temperature.
• Provide enough space for good air flow.
• Do not install the Controller directly above equipment that generates a large amount of heat such
as heaters, transformers, or high-capacity resistors.
• If the ambient temperature exceeds 55°C, install a cooling fan or air conditioner.
Control
panel
Louver
l Accessibility for Operation and Maintenance
• To ensure safe access for operation and maintenance, separate the Controller as much as possi-
ble from high-voltage equipment and power machinery.
• It will be easy to operate the Controller if it is mounted at a height of 1.0 to 1.6 m above the floor.
l Improving Noise Resistance
• Do not mount the Controller in a control panel containing high-voltage equipment.
• Install the Controller at least 200 mm away from power lines.
Power lines
200 mm min.
• Ground the mounting plate between the Controller and the mounting surface.
5-12
Fan
NX-series
Controller
NX-series
Controller
200 mm min.
NX-series NX1P2 CPU Unit Hardware User's Manual (W578)