Purpose; Part Names And Functions - Omron NX1P2 Series Hardware User Manual

Machine automation controller
Hide thumbs Also See for NX1P2 Series:
Table of Contents

Advertisement

3-4-2

Purpose

The Analog I/O Option Board allows inputs from devices such variable resistors and process-control
sensors. It also enables you to control inverters.
Analog inputs that can be processed are 0 to 10 V inputs from devices including variable resistors,
and 4 to 20 mA inputs from process-control sensors.
Analog output range from 0 to 10 V, which allow the CPU Unit to control inverters directly.
Refer to the NX-series NX1P2 CPU Unit Built-in I/O and Option Board User's Manual (Cat. No. W579)
for details on how to use the Option Boards.
3-4-3

Part Names and Functions

Analog Input Option Board (NX1W-ADB21)
Status indicator
ERR
IN
Analog input terminal block
l Status Indicator
Indicator
ERR
l Analog Input Terminal Array
Precautions for Correct Use
When you use the current input, be sure to short-circuit V I1 with I I1, and short-circuit V I2 with
I I2.
NX-series NX1P2 CPU Unit Hardware User's Manual (W578)
Color
Status
Red
Lit.
An Option Board error (WDT) was detected by the self-diagnostic func-
tion.
Flashing.
A communications error occurred between the Option Board and the
CPU Unit.
Not lit.
Normal operation
Abbrevia-
Signal name
tion
V I1
Voltage input 1
I I1
Current input 1
V I2
Voltage input 2
I I2
Current input 2
COM
Input common
3 Configuration Units
Description
3
3-27

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nx1p2 1 series

Table of Contents