Omron NX1P2 Series Hardware User Manual page 25

Machine automation controller
Hide thumbs Also See for NX1P2 Series:
Table of Contents

Advertisement

because the output terminals on Output Units may momentarily turn ON when power supply is
turned ON to the Controller.
• If you transfer data from a backup file on an SD Memory Card to the Controller when the power sup-
ply is turned ON, properly select the data groups to transfer. If the data for an unintended data group
is transferred to the Controller, it may cause the equipment to operate unpredictably.
• You cannot obtain normal input data from NX Units while the Units are restarting. Use the system-
defined variables or device variables for the NX Units on the CPU Unit in the user program to check
the validity of the I/O data before you attempt control operations.
Actual Operation
• If you change the fail-soft operation setting, the output status when the error occurs may also
change. Confirm safety before you change the setting.
• If you use fail-soft operation, write programming to determine whether Unit I/O data is valid. Without
such programming, the user program cannot distinguish between Units for which I/O refreshing is
continued and Units for which I/O refreshing is stopped.
Turning OFF the Power Supply
• Never turn OFF the power supply to the Controller when the BUSY indicator is flashing. While the
BUSY indicator is lit, the user program and settings in the CPU Unit are being backed up in the built-
in non-volatile memory. This data will not be backed up correctly if the power supply is turned OFF.
Also, a major fault level Controller error will occur the next time you start operation, and operation
will stop.
• Do not turn OFF the power supply or remove the SD Memory Card while SD Memory Card access
is in progress (i.e., while the SD BUSY indicator flashes). Data may become corrupted, and the
Controller will not operate correctly if it uses corrupted data. To remove the SD Memory Card from
the CPU Unit while the power supply is ON, press the SD Memory Card power supply switch and
wait for the SD BUSY indicator and SD PWR indicator to turn OFF before you remove the SD Mem-
ory Card.
• Do not disconnect the cable or turn OFF the power supply to the Controller when downloading data
or the user program from Support Software.
• Always turn OFF the power supply to the Controller before you attempt any of the following.
a) Mounting or removing the Units
b) Assembling the Units
c) Setting DIP switches or rotary switches
d) Connecting cables or wiring the system
e) Connecting or disconnecting the terminal blocks or connectors
f) Mounting or removing the Option Boards
The Power Supply Unit may continue to supply power to the rest of the Controller for a few seconds
after the power supply turns OFF. The POWER indicator is lit during this time. Confirm that the
POWER indicator is not lit before you perform any of the above.
Operation
• Confirm that no adverse effect will occur in the system before you attempt any of the following.
NX-series NX1P2 CPU Unit Hardware User's Manual (W578)
Precautions for Safe Use
23

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nx1p2 1 series

Table of Contents