4.13 CUSTOM CONTROL EQUATION LISTING

The Custom Control Equation Listing displays the line by line Custom Control
equations for the system.
--------------------------------------------------------------------------------
XYZ BUILDING
2796 node:1 rev:6
--------------------------------------------------------------------------------
Program: 7
Label: AUTO LED
COMMENTS:
INPUTS:
OR the ON state of:
P1024
P2
P1027
OUTPUTS:
TRACK points ON pri=9,9
16-152
END:
Label: ALERT/EVAC DELAY - NORMAL - 10 MINS
COMMENTS:
AS 2220.1 STATES THE DELAY BETWEEN ALERT AND EVAC MUST NOT EXCEED 10
MINUTES
INPUTS:
NOT the ON state of:
P5
OUTPUTS:
SET to value 600 (Secs) the analogs:
A267
END:
Label: ALERT/EVAC DELAY - SERVICE - 15 SECS
COMMENTS:
INPUTS:
The ON state of:
P5
OUTPUTS:
SET to value 15 (Secs) the analogs:
A267
END:
Label: * ENABLE alert/evac/cascade OPERATION *
COMMENTS:
INPUTS:
The ON state of:
A34
OUTPUTS:
HOLD points ON pri=9,9
P1036

Table 17 CUSTOM CONTROL EQUATION LISTING

Document No.: 4100-M011
CUSTOM CONTROL EQUATION LISTING
UTILITY
KEYSWITCH - AUTO
UTILITY
FRONT PANEL LAMPTEST CONTROL (ANNUNC. 0)
UTILITY
KEYSWITCH - AUTO LED
UTILITY
Ann 0 Pt 152 LED/SW Spec Output
UTILITY
SET SERVICE PSEUDO VALUES
ANALOG
ALERT/EVAC CHANGEOVER VALUE
UTILITY
SET SERVICE PSEUDO VALUES
ANALOG
ALERT/EVAC CHANGEOVER VALUE
TIMER
SYSTEM STARTUP PULSE TIMER
UTILITY
ENABLE CASCADE OPERATION
March 1998
SIMPLEX 4100 EWIS
INSTALLATION MANUAL
Page 156
14:41:55, WED, 25-MAR-98
CUSTOM CONTROL
EQU DETAIL
Program: 7
Equation 1
Equation 2
Equation 3
Equation 4
Issue 1.0