Page 48
3.8.1 Network WIP Phone Termination – Master Node
The WIP Master Phone is terminated on connector P6. Only use approved master
phone part number 2084-9106.
The next node in the network is terminated on connector P4.
The last node in the network is terminated on connector P3.
Not Used
P5
4100-0205
IC
P6
Master
Phone
Handset

Figure 20 WIP Network Master Node Phone Terminations

The Master Phone Handset terminations are on terminals labelled 1 & 2.
The positive line on terminal 1 and the negative line on terminal 2.
Document No.: 4100-M011
From Last Node
in Network
1 2 3 4 5 6 7 8
TB1
P3
Power
&
Communication
connections
Not Used
March 1998
INSTALLATION MANUAL
To First Node
in Network
P4
SIMPLEX 4100 EWIS