Placing System Into Operation; Power Up Procedures - Simplex 4100 Installation Manual

Emergency warning and intercommunication system (ewis)
Table of Contents

Advertisement

SIMPLEX 4100 EWIS
INSTALLATION MANUAL

5. PLACING SYSTEM INTO OPERATION

Before undertaking any activities inspect the interior visually and check that all panel
equipment is securely mounted, and that all cables are connected at the appropriate
points.

5.1 POWER UP PROCEDURES

When power is first applied to the panel, or when the processor has been reset, the
system will self-test the integrity of its memory and verify proper card installation. At
the end of the self-test, the system will display "SYSTEM STARTUP IN PROGRESS"
followed by at least two fault conditions (battery and time and date). After the battery
is connected and the time and date has been entered, the system should then
display the message "SYSTEM IS NORMAL" along with the time and date.
Notes:
(i)
When a printed circuit board is not properly inserted, the system will
display a fault condition.
(ii)
When a printed circuit board is inserted, but configured incorrectly or
not defined in software, the system will display a fault condition, normal
operation will be suspended for that card until the fault has been
corrected.
(iii) Other failures will cause a message to be displayed to the operator,
may cause the system to become inoperative and the tone alert to
sound continuously.
Refer Appendix A for a list of Fault Messages and likely causes and
rectification
Document No.: 4100-M011
March 1998
Page 65
Issue 1.0