SIMPLEX 4100 EWIS
INSTALLATION MANUAL

9.4 ANNUNCIATOR TROUBLES

If the LCD displays ...
Card X, Led (Switch) Display Slot X
Card Defined But Not Inserted
Annunciator Display Card Programmed in Software but not connected via the
Ribbon Cable.
If the LCD displays ...
Card X, Led (Switch) Display Slot X
Card Not Defined But Inserted
Annunciator Display Card not Programmed in Software but connected via the
Ribbon Cable.
Check ribbon cable or Verify Annunciator Programming.